| To order your Standby Generator System - Call Toll Free 888-GENITUP (888-436-4887) | ||||
QT150 |
GENERAC QT150 Liquid Cooled Gas Engine Generator Sets |
Standby Power Rating |
|
![]() |
GENERAC 6.8L ENGINE |
STANDARD EQUIPMENT |
|||||||||||||||||||||||||
|
|
||||||||||||||||||||||||
FEATURES |
|||||||||||||||||||||||||
|
|
||||||||||||||||||||||||
APPLICATION & ENGINEERING DATA |
|||||||||||||||||||||||||
GENERATOR SPECIFICATIONS VOLTAGE REGULATOR GENERATOR FEATURES
CONTROL PANEL FEATURES TWO FOUR LINE LCD DISPLAYS READ:
INTERNAL FUNCTIONS:
|
|||||||||||||||||||||||||
| Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271). | |||||||||||||||||||||||||
OPERATING DATA - QT150 |
|||
| KW RATING | 150 | ||
| ENGINE SIZE | 6.8 Liter V-10 | ||
| GENERATOR OUTPUT VOLTAGE/KW - 60 Hz | KW |
AMP | CB Size |
| 120/240V, 1-phase, 1.0 pf
120/208V, 3-phase, 0.8 pf 277/480V, 3-phase, 0.8 pf |
150
150 150 |
625
520 226 |
700
600 250 |
| GENERATOR LOCKED ROTOR KVA AVAILABLE @ VOLTAGE DIP OF 35% Single phase or 208 3-phase 480V 3-phase |
320 350 |
||
| ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) | Natural Gas |
Propane | |
| (ft3/hr.) | (gal/hr.) | cu ft/hr | |
| Exercise cycle 25% of rated load 50% of rated load 75% of rated load 100% of rated load |
155 556 1070 1491 2061 |
1.70 6.06 11.72 16.33 22.57 |
62.6 224.1 431.3 600.9 830.6 |
| ENGINE COOLING Air flow (inlet air including alternator and combustion air) ft3/min. Coolant capacity - US gal. Heat rejection to coolant BTU/hr. Max. operating air temp. on radiator °C (°F) Max. ambient temperature °C (°F) |
7800 4.5 568,000 60 (150) 50 (140) |
||
| COMBUSTION AIR REQUIREMENTS Flow at rated power 60 Hz cfm |
410 |
||
| SOUND EMISSIONS IN DBA Exercising at 7 meters Normal operation at 7 meters |
66 79 |
||
| EXHAUST Exhaust flow at rated output 60 Hz cfm Exhaust temp. at muffler outlet °F |
1535 1100 |
||
| ENGINE PARAMETERS Rated synchronous RPM 60 Hz HP at rated KW 60 Hz |
3600 254 |
||
POWER ADJUSTMENT FOR AMBIENT CONDITIONS 3% for every 10 °C above - °C Altitude Deration 1% for every 100 m above - m |
25 77 182 600 |
||
|
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. kW rating is based on LPG fuel and may derate with natural gas.
|
|||
BSA Power Solutions e-mail: Generator Sales Department BSA Power Solutions installs and services Briggs & Stratton Natural Gas and Propane (LP Gas) Standby Generators to all the Miami Dade County: Miami Gardens - Aventura - Golden Beach - Sunny Isles Beach - North Miami Beach - North Miami - Bal Harbour Broward Communities: Coconut Creek - Cooper City - Coral Springs - Dania Beach - Davie - Deerfield Beach - Fort Lauderdale - Hallandale Palm Beach Cities, Counties and Municipalities: Atlantis - Belle Glade - Boca Raton - Boynton Beach - Briney Breezes - Cloud Lake - Delray Beach - Glen Ridge - Golf |
Copyright © 2012 BSA Power Solutions, Inc. All rights reserved