QT070

GENERAC QT070 Liquid Cooled Gas Engine Generator Sets


Standby Power Rating
70 kW 60 Hz

GENERAC QT070 70kW Liquid Cooled Gas Engine Generator for large homes and Buildings

GENERAC - 6.8L ENGINE
Naturally Aspirated - Gaseous Fueled

STANDARD EQUIPMENT

 

  • All input connections in one single area
  • High coolant temperature shutdown
  • Low oil pressure shutdown
  • Low coolant level automatic shutdown
  • Low fuel pressure
  • Overspeed automatic shutdown
  • Adjustable cranking timer
  • Adjustable exercise timer
  • Oil drain extension
  • Cool flow radiator
  • Closed coolant recovery system
  • UV/Ozone resistant hoses
  • Watertight state of the art electrical connectors
  • Mainline circuit breaker
  • Oil drain extension to frame rail
  • Radiator drain extension
  • Battery charge alternator
  • 2 Amp static battery charger
  • Battery and battery cables
  • Battery rack
  • Fan and belt guards
  • Isochronous governor

FEATURES

 

  • Innovative design and fully prototype tested
  • UL2200 Listed
  • Solid state frequency compensated digital
    voltage regulator
  • Dynamic and static battery charger
  • Sound attenuated acoustically designed enclosure
  • Quiet test for low noise level exercise
  • Acoustically designed engine cooling system
  • High flow low noise factory engineered exhaust system
  • State of the art digital control system with H-100 microprocessor control panel
  • Built-in kW, kVAR and power factor meters
  • Watertight electrical connectors
  • Rodent proof construction
  • High efficiency, low distortion Generac designed alternator
  • Vibration isolated from mounting base
  • Matching Generac transfer switches engineered and tested to work as a system
  • All components easily accessible for maintenance
  • Electrostatically applied powder paint

APPLICATION & ENGINEERING DATA


Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514, ISO3046 and DIN6271). (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

OPERATING DATA


KW RATING 70

ENGINE SIZE 6.8 Liter V-10

GENERATOR OUTPUT VOLTAGE/KW - 60 Hz

KW

AMP CB Size
120/240V, 1-phase, 1.0 pf
120/240V, 3-phase, 0.8 pf
120/208V, 3-phase, 0.8 pf
277/480V, 3-phase, 0.8 pf
70
70
70
70
292
210
243
105
300
250
300
125

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%

Single phase or 208-240 3-phase
480V 3-phase


145
160

ENGINE FUEL CONSUMPTION (Natural Gas) (Propane) Natural Gas
Propane
  (ft3/hr.) (gal/hr.) cu ft/hr
Exercise cycle
25% of rated load
50% of rated load
75% of rated load
100% of rated load
110
260
499
696
1020

1.20
2.85
5.46
7.62
11.17
44.2
104.9
200.9
280.4
411

ENGINE COOLING
Air flow (inlet air including alternator and combustion air) ft3/min.
System coolant capacity US gal.
Heat rejection to coolant BTU/hr.
Max. operating air temp. on radiator °C (°F)
Max. ambient temperature °C (°F)

5200
4.5
287,000
60 (150)
50 (140)

COMBUSTION AIR REQUIREMENTS
Flow at rated power 60 Hz cfm
  205  

SOUND EMISSIONS IN DBA
Exercising at 7 meters
Normal operation at 7 meters
 
61
65
 

EXHAUST
Exhaust flow at rated output 60 Hz cfm
Exhaust temp. at muffler outlet °F
 
557
890
 

ENGINE PARAMETERS
Rated synchronous RPM 60 Hz
HP at rated KW 60 Hz
 
1800
110.7
 

POWER ADJUSTMENT FOR AMBIENT CONDITIONS
Temperature Deration

3% for every 10 °C above - °C
1.65% for every 10 °F above - °F

Altitude Deration

1% for every 100 m above - m
3% for every 1000 ft. above - ft.

 


25
77



183
600
 

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and specifications are subject to change without notice. kW rating is based on LPG fuel and may derate with natural gas.


GENERAC ® POWER SYSTEMS, INC. • P.O. BOX 8 • WAUKESHA, WI 53187
262/544-4811 • FAX 262/544-4851
© 2008 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.

 


Warning: include(/home/bsapower/public_html/includes/footer.php) [function.include]: failed to open stream: No such file or directory in /home/bsaent/public_html/pages/Generac/70kWGeneracGenerator.php on line 440

Warning: include() [function.include]: Failed opening '/home/bsapower/public_html/includes/footer.php' for inclusion (include_path='.:/usr/lib/php:/usr/local/lib/php') in /home/bsaent/public_html/pages/Generac/70kWGeneracGenerator.php on line 440